8
7-1/8" (181 mm) Dia.
Vertical Adjustment:
5/8" (16 mm) to
2 7/8" (73 mm)
2" (50 mm) max.
Ceiling Thickness
8-5/8" (200 mm) Dia.
9-7/8"
(251 mm)
Top View
(Magnetic Ballast)
18-5/8" (473 mm)
10-7/8"
(276 mm)
10-1/2"
(267 mm)
8-1/4"
(210 mm)
20" (508 mm) to 30" (762 mm)
9-3/4"
(248 mm)
Top View
(Electronic Ballast)
10-7/8"
(276 mm)
9-3/4"
(248 mm)
20" (508 mm) to
30" (762 mm)
11" (280 mm)
(100/150W)
Calculite
®
HID Wall Wash C7E17OW
Page 1 of 2 7” Aperture, ED17 (Open Rated) Ceramic Metal Halide
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Group LLC • B1004
Features
1. Downlight/Wall Washer Reflector Trim: Anodized aluminum, 0.040” (16-
ga.). Provides vertical surface wall washing and medium beam downlighting;
50° visual cut-off to lamp and lamp image; self-flange in painted white or
aperture-matching polished flange. Consult factory for other finishes.
2. Socket Housing: Galvanized steel, pre-wired with medium base pulse rated
socket. Snaps onto upper reflector for secure attachment without tools;
assures proper lamp alignment to optics for consistent performance.
3. Mounting Frame: 0.048" (18-ga.) galvanized steel includes pre-installed
mounting bars.
4. Mounting Ring: 0.048" (18-ga.) galvanized steel. Designed for vertical
adjustment from above or below for ceilings from 0" to 2" thick. Center-line
notches allow consistent alignment of multiple fixtures.
5. Retention Springs: Rust resistant springs secure reflector in place for quick,
tool-less installation.
6. Frame Vertical Adjustment Mechanism: Vertical adjustment mechanism
accommodates mounting to virtually any ceiling system using pre-installed
mounting bars, or 1/2" EMT tubing (by others). Single locking feature secures
all adjustments. Alignment holes and markings allow fixture to be pre-set
prior to installation.
7. Mounting Bars: 0.048" (18-ga.) Pre-installed, telescoping bars extend to 30"
long and lock securely into position. Built-in locking tabs provide positive
attachment to common T-bar systems. Self-centering feature simplifies
installation in 24" O.C. grid systems. Attaches to steel or wood joists without
accessories.
8. Ballast: Electronic 120V or 277V. Magnetic dual voltage (120V & 277V).
Accessible from below for inspection and/or replacement without tools.
9. Junction Box: 0.059" (16-ga.) galvanized steel. UL listed for 8 No. 12 AWG,
90°C through branch circuit conductors; allows inspection from below.
10.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not
install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor, T.H.D.
<15%, thermally and transient protected, RMI / RFI complies with FCC Part 18
non-consumer equipment, shut-down circuit at end of lamp life, sound rating
"A", -5°F (-20°F for 150W) minimum starting temperature, Type 1 outdoor rating.
Electrical (cont)
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 0.67/0.28 78
100W MH M90/M140 120/277 0.90/0.43 110
150W MH M102 120/277 1.40/0.61 167
Magnetic Ballast: 120V/277V dual voltage, 60 Hz., encased and potted,
HX-HPF circuit type, high power factor, sound rating “B”, -20°F minimum starting
temperature, Type 1 Outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 1.90/0.80 94
100W MH M90/M140 120/277 2.40/1.10 125
150W MH M102 120/277 3.70/1.60 180
Options and Accessories
Fuse: Add suffix F1 or F2 to Frame-In Kit (F1=120V, F2=277V)
Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Damp Locations), I.B.E.W.
For 150W, install fixtures with minimum spacing between:
1. Center-to-center of adjacent luminaries: 3 feet.
2. Top of luminaire to overhead building member: 3 inch.
3. Luminaire center to side building member: 1 1/2 feet.
Reflector Trim Frame-In Kit Lamp
(Coated, Ceramic MH)
C7E17OW CLW Specular Clear, White Painted Flange. C770MHOE1 Electronic 120V / C770MHOE2 Electronic 277V 70W E17, ED17, BD17 (Open Rated)
CLP Specular Clear, Matching Flange. C710MHOE1 Electronic 120V / C710MHOE2 Electronic 277V 100W E17, ED17, BD17 (Open Rated)
CCDW Comfort Clear Diffuse, White Painted Flange. C715MHOE1 Electronic 120V / C715MHOE2 Electronic 277V 150W E17, ED17, BD17 (Open Rated)
CCDP Comfort Clear Diffuse, Matching Flange. C770MHOU Magnetic 120V/277V 70W E17, ED17, BD17 (Open Rated)
CCZW Champagne Bronze, White Painted Flange. C710MHOU Magnetic 120V/277V 100W E17, ED17, BD17 (Open Rated)
CCZP Champagne Bronze, Matching Flange. C715MHOU Magnetic 120V/277V 150W E17, ED17, BD17 (Open Rated)
Ceiling Cutout: 8” (203mm) Dia.
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - HID Wall Wash C7E17OW

815 3 9 726487-1/8" (181 mm) Dia.Vertical Adjustment: 5/8" (16 mm) to 2 7/8" (73 mm)2" (50 mm) max.Ceiling Thickness8-5/8" (2

Seite 2

Calculite®HID Wall Wash C7E17OWPage 2 of 2 7” Aperture, ED17 (Open Rated) Ceramic Metal Halide Lightolier a Genlyte company www.lightolier.com631 Airp

Kommentare zu diesen Handbüchern

Keine Kommentare