Lightolier L1PH Series Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Netzteile Lightolier L1PH Series herunter. Lightolier L1PH Series User's Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 2
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
Unit 14.0 kVA
Battery 2,995 lbs.
Cabinet (1,358 kg)
Electronics 465 lbs.
Cabinet (211 kg)
Total System 3,460 lbs.
(1,569 kg)
L1PH Series Uninterruptible Power Supplies
L1PH
Page 1 of 2 14.0 kVA Single Phase UPS System
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier
a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Overall Characteristics
86% throughput efficiency
Operating temperature range 32°F (0°C) to 104°F (40°C)
Internal maintenance by-pass is standard
Main load disconnect switch standard
Double conversion, no interruption
Standard backup time of 90 minutes, other run times optional
Output circuit breakers and normally-off loads optional
Housing
Free standing, NEMA 1 enclosure
Acid resistant powder coat finish
Multiple conduit entries
Metering/Controls
Standard
Alpha-numeric front panel display with 14 metered measurements and
53 messages/alarms
Normal, caution and alarm indicating LEDs
Audible failure alarms with silence switch
Dry contact for remote failure alarm
“D” type 9-pin computer interface connector (see pin config. on back)
Programmable battery monitor with alarm
Optional
Diagnostics software for remote computer (PC) monitoring and control
Stand-alone remote display mimics all measurements, indications and
alarms shown on the front panel display
Additional RS-232 input/output port for remote monitoring and system
control
Electrical
Sine Wave Output
Completely solid-state Pulse Width Modulation (PWM) inverter
16-bit microprocessor control
Input power factor correction maintains power factor at 0.99
Transient response 5%; Recovery time, 10 mS (100% load step)
3:1 crest factor capability
Inverter output distortion 2.5% THD (at unity power factor)
Output voltage regulation ±6% of nominal at full load
Frequency within ±0.05% of nominal
Inverter efficiency 84%
Load power factor capability is 0.5 leading to 0.5 lagging
(Continued on page 2)
NOTE: Input circuit
breaker not available.
Input switch is
standard.
L1PH I 14.0 S
SERIES INPUT SYSTEM BASE BATTERY OUTPUT OUTPUT # ON 2ND NORMALLY # OF NOL
VOLTAGE TYPE SIZE TYPE VOLTAGE CKT BRKRS
1
VOLTAGE OFF LOAD NOL VOLTAGE
L1PH = Single
Phase
Uninterruptible
Power
Supplies
14.0 = 14.0 kVa
2 = 208 V
3 = 240 V
4 = 277 V
Z = Special
Voltage
(Consult
Factory)
1 = 120 V
2 = 208 V
3 = 240 V
4 = 277 V
5 = 120/208 V
6 = 120/240 V
7 = 120/277 V
Z = Special
Voltage
(Consult
Factory)
Y = Hardwire
A = 1 0CB
B = 2 0CB
C = 3 0CB
D = 4 0CB
E = 5 0CB
F = 6 0CB
G = 7 0CB
H = 8 0CB
J = 9 0CB
K = 10 0CB
L = 11 0CB
M = 12 0CB
N = OCBA1
P = OCBA2
R = OCBA3
S = OCBA4
T = OCBA5
U = OCBA6
V = OCBA7
W = OCBA8
X = OCBA9
0
1
2
3
4
5
6
7
8
9
10
11
A = No
B = Yes
C = Yes w/ Time
Delay Timer
0 = No NOL
Y = Hardwire
Terminal
1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
11 = 11
12 = 12
X = None
A = 1st
B = 2nd
I = ETL Listed
to UL 924 for
Emergency
Lighting
Applications
S = Sealed
Lead Calcium
34.0”
86.4 cm
33.0”
83.8 cm
70.0”
177.8 cm
Battery
Cabinet
33.0”
83.8 cm
30.0”
76.2 cm
43.5”
110.5 cm
Electronics
Cabinet
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - Job Information Type:

Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp typ

Seite 2 - AVAILABLE

Electrical (continued from page 1)• Automatic, battery protecting low voltage disconnect (LVD)• Advanced battery diagnostics and management system• Te

Kommentare zu diesen Handbüchern